Dry Chemical (Stored Pressure) (PORTABLE TYPE) (CONFoRMING TO IS:15683:2018)

DCP/SP-044

DCP/SP-045

DCP/SP-046

DCP/SP-047

DCP/SP-048



Technical Specification
Product Code No. DCP/SP-044 DCP/SP-045 DCP/SP-046 DCP/SP-047 DCP/SP-048
Description Capacity (Kg) 1 2 4 6 9
Type of Fire ABC ABC ABC ABC ABC
Type of Extinguisher DCP (Mono Ammonium Phosphate) IS:4308
Expellent Pressurized with Dry Nitrogen
Min. Effective Discharge(%) 85 85 85 85 85
Min. Jet Length(mtr) 2-3 2-3 3-4 3-4 4-5
Discharge Time (sec.) 8-10 8-10 10-13 13-18 18-20
Working Pressure (Kgf/cm2) 15 15 15 15 15
Hydraulic test Pressure(Kgf/cm2) 35 35 35 35 35
Brusting Pressure (Kgf/cm2) 55 55 55 55 55
Operating Pressure Upright Upright Upright Upright Upright
Operating Valve Squezze Grip Type with Nozzle Squezze Grip Type with Discharge Hose and Nozzle
Fire Rating 1A, 21B 1A, 21B 2A, 55B 3A, 89B 4A, 144B
Temperature (deg C) -10°c + 60°c -10°c + 60°c -10°c + 60°c -10°c + 60°c -10°c + 60°c
Note: Also Available in UL listed Powder
Application:
CLASS A FIRE: Wood, Textiles, Paper, Cloths, Cotton Mill, Jute Mill etc.
CLASS B FIRE: Petroleum, Oil, Diesel, Paint, Varnish, Solvent, Aviation Fuel, Flammable and Volatile Liquid etc.
CLASS C FIRE: Flammable Gases Live Electrical Equipments, Industrial Gases, Electrical Installation, Power Grid and Computer Room etc.